Power factor and the electricity bill

2026-11-28 · 2 min read

The power that does work is real power. But capacity and the demand charge attach to apparent power, which is larger. Power factor is what separates them.

Three kinds of power

Real power (P, kW) does the work. Reactive power (Q, kvar) builds and collapses magnetic fields without doing work. Apparent power (S, kVA) is their magnitude combined.

S² = P² + Q² and power factor is P ÷ S. At 1.0, S equals P; at 0.86, S is about 1.16 times P.

In practice a power factor of 0.9 or better is expected, sometimes through the tariff. A low factor needs more capacity for the same work and increases line losses.

What the demand charge follows

A bill has two parts: an energy charge on kWh consumed and a demand charge on contracted or maximum demand in kW.

Contracted demand usually follows apparent power or maximum demand. So when the power factor drops, apparent power rises and the demand charge rises with it while the energy consumed stays the same.

The template simplifies this: the demand charge is apparent power × unit charge, and the saving is the difference after correction.

The saving in numbers

250 kW at 0.86 gives 290.70 kVA, and at 8,320 per kW a demand charge of 2,418,605 a month.

Correcting to 0.95 gives 263.16 kVA and 2,189,474 — a saving of 229,131 a month, about 2.75 million a year.

The energy charge is computed on real power, so it does not fall. The saving comes from the demand charge alone.

S        = P / pf
basic    = S * demand_charge
S_fixed  = P / pf_target
saving   = (S - S_fixed) * demand_charge
# 250/0.86 = 290.70 kVA  →  basic 2,418,605
# 250/0.95 = 263.16 kVA  →  basic 2,189,474

How it is corrected, and at what cost

Correction usually means capacitor banks that supply the reactive power locally. Since it is a capital cost, compare it with the saving and compute a payback.

Capacitor size comes from the reactive power needed: Q = P × (tan(cos⁻¹ PF₁) − tan(cos⁻¹ PF₂)). Oversizing leads to leading power factor, which can cost more than it saves.

The template's cumulative node adds the monthly saving over 36 months: 229,131 × 36 = 8,248,715, which can be set against the investment.

ItemPF 0.86PF 0.95Difference
Apparent power290.70 kVA263.16 kVA−27.54 kVA
Monthly demand charge2,418,6052,189,474−229,131
Monthly energy charge5,280,0005,280,0000
36-month cumulative saving——8,248,715

Limits of the model

The model assumes the demand charge is proportional to apparent power. Real tariffs have demand brackets, time-of-use rates and load-factor adjustments, so proportionality is an approximation.

Correction also needs equipment, and the optimal size shifts with the load. Use these numbers for direction; the design itself needs an electrical engineer.

Questions

Is a higher power factor always better?

Broadly yes, but avoid over-correction: an oversized capacitor bank produces leading power factor, which brings its own losses and penalties.

Does the energy charge change with power factor?

It is billed on kWh, so directly no. Lower line losses can shave a little off actual consumption.